Prerequisites: You have secured the required licenses and the station databases are ready to install.
- After installing
Niagara 4 on the
Supervisor PC and starting
Workbench, open a platform connection to the
AX-3.8
Supervisor station and stop the station.
- At the
N4.0
Supervisor PC (with access to
N4.0-migrated station folders), install and start the
N4.0 platform daemon.
For example, from the Start menu, select All Programs >
Niagara 4 4.0.3
In some cases, this daemon may already be running; however re-installing causes no issues.
- Start
Workbench (if not already started) and click .
The Options window opens.
- Set
Copy Remote Station Alarm Data and Copy Remote Station History Data to true, and click OK
- Open a local platform connection
(in the Nav tree, right-click My Host, and choose Open Platform).
- After platform login, go to the Station Copier platform view.
Ready-to-install migrated stations are on the left side, in your
Workbench User Home, and there is no station installed on the right side, in the daemon user home (localhost).If your migrated station folders are not on the left side,
copy them into your User Home. For example in: C:\Users\userName\Niagara4.x\<brand>\stations
- Select the migrated
Supervisor station, and copy (install) to the daemon user home.
- To transfer in this station copy, choose to
Copy files from selected directories, and START AFTER INSTALL... and AUTO-START... and click Next. As shown below, select all station folders
- Select all station folders to be transferred and click .