4. Connecting from the Supervisor to the NiagaraAX-3.8 legacy security station

The following task describes how to connect from a configured legacy controller station (running NiagaraAX-3.8) to a properly configured Niagara Enterprise Security 2.4 Supervisor.
Prerequisites: The legacy controller station has completed a user login to the Niagara Enterprise Security 2.4 Supervisor station.
Perform the following steps:
  1. In the browser, connect to the Supervisor and navigate to the station database view (System Setup > Remote Devices > Station Management)
  2. Select the remote NiagaraAX-3.8 legacy security station and click the Edit icon (Image). These fields should already be populated. Verify the fields and click Continue to Remote Configuration.
    The Remote Configuration window opens.
    Image
  3. Enter the newly created user credentials and click Ok.
    The Remote Configuration window closes, the configure job runs and establishes the connection with the correct relationship between Supervisor and subordinate. You are ready to proceed with station Join and Replicate procedures.
Once the Niagara Enterprise Security 4.8 Supervisor station connects to the NiagaraAX-3.8 legacy station, no further migration of the legacy station is required. The legacy station cannot be migrated to Niagara Enterprise Security 4.8 until the JACE-6 is replaced with newer hardware.