Meters tested

Each meter was tested for its minimum poll interval.

The property, Max Inputs Per Cycle Count, shows the maximum number of additional inputs in a single cycle of a device. This property appears in a hidden slot. The test used the value of this property to calculate the minimum poll interval as follows:

Minimum poll interval = (Max Inputs Per Cycle Count +2) x (interval times + timeout periods)

Thus, with an interval time of five seconds, a timeout of one second, and a maximum number of data requests of 20, the minimum poll interval should be 72 seconds.

Sensus PolluTherm

Cycle count set to 1

Reset Required set to true

Mbus Connection to terminals 24 & 25

Baud rate of 300 or 2400 used

Maximum number of additional inputs in a complete cycle is 6

Time interval can be set down to 1 second at 2400 Baud (subject to other meters on the network)

Sensus website, www.sensusesaap.com

Sensus HRI-B2

Cycle count set to 1

Reset Required set to true

Baud rate of 300 or 2400

Maximum number of additional inputs in a complete cycle is 0

Time interval can be set down to 1 second at 2400 Baud (subject to other meters on the network)

Sensus website, www.sensusesaap.com

Sensus PolluCom E

Cycle count set to 1

Reset Required set to true

Baud rate of 300 or 2400

Maximum number of additional inputs in a complete cycle is 19

Time interval can be set down to 1 second at 2400 Baud (subject to other meters on the network)

Sensus website, www.sensusesaap.com

Kamstrup Multical

Baud rate of 300 or 2400

Cycle count set to 1.

Reset Required set to true.

Maximum number of additional inputs in a complete cycle is 0

Time interval of 12 seconds has been found to be required, for baud rate of 300

Manufacturer Specific Data is supported.

Kamstrup website, www.kamstrup.com

PEWO Station

Requires a baudrate of 2400

Endress+Hauser RMS621

This is a sophisticated design and can be programmed for different message inputs.

Endress+Hauser website, www.endress.com

NZR Apartment water Meter WZ-M-Modularis

Baud rate of 2400

Cycle count set to 1

Reset Required set to false.

Device Fc Bit In Use set to true

NZR website, www.nzr.de

NZR Heat Meter WZ-HY

Baud rate of 2400

Cycle count set to 1.

Reset Required set to false.

NZR website, www.nzr.de

Relay PadPuls M2

Baud rate of 300,2400 and 9600

Cycle count set to 1.

Reset Required set to false.

Relay website, www.relay.de

 
NOTE: Manufacturer-specific data are NOT supported on this device. These data are not defined in the manufacturer’s specification.