New (or edit) device window

This window configures individual Mbus devices.
Figure 8.   Edit Device window
Image
Property Value Description
Model Name text Identifies the model of the meter.
Name text Identifies the name given to the meter.
Primary Address 0 to 250 Defines a unique number for each device.
Secondary Address number Defines an alternate number to identify each device.
Address Mode drop-down list Indicates which address to use: Primary, Secondary or Secondary Extended.
Mbus Config additional properties See Mbus Config.
Cycle Quantity number Identifies the number of message commands required to obtain all messages from a device.
Reset Required (optional) true or false (default) Defines if the device requires a reset to be output prior to requesting messages.
Search Fc Bit State true (default) or false Refers to data transmitted from the slave device to the master, and functions with the Search Fc Bit in Use property.

true indicates that a follow-on message contains the next set of data. In other words, the slave has more data to communicate to the master than fits into a single message.

FC stands for Frame Count.

Search Fc Bit in Use true (default) or false Refers to data transmitted from the slave device to the master, and functions with the Search Fc Bit State property.

true indicates that the Search Fc Bit State should be evaluated for additional data.

Not all devices need to implement this, and those that do declare within the message if the mechanism is active or not.

Ident Number read-only Reports the number contained in each communication message received from the device.
Manufacturer read-only Identifies the device manufacturer. This code is contained in the communication messages from this device.
Version Number read-only Identifies the manufacturer's version number that defines the device.
Device Type ID drop-down list Defines the device type. This information is found in the communication messages from this device.
     
Baud Rate read-only Reports the baud rate configured for the device.
Enabled true (default) or false Enables and disables the device.

Mbus Config

These properties allow for device-specific timing overrides, which the driver uses to communicate with a device. When the driver discovers devices, it automatically enters and enables the timings that worked. You may further customise these timings on each device as necessary. To batch edit multiple identical devices, select the devices in the Mbus Device Manager, and use the edit function.