BACnet Network view, BacNet Network tab

This view configures BACnet network settings in the system.
Figure 194.   BACnet Network view
Image

To access this view, click Controller Setup > Remote Devices > BACnetNetwork.

The Save button saves configuration changes. The Rebuild BACnet Records button recreates all integrated BACnet records. This button is useful if you have a problem with BACnet point automation.

Properties

In addition to the standard properties (Enabled, Status, and Fault Cause), these properties support a BACnet network.

Property Value Description
Object Id number with valid range from 0 to 4194302; defaults to -1 resulting in no device Specifies a numerical device ID on the BACnet network (must be unique among all BACnet devices).
Apdu Segment Timeout milliseconds; defaults to recommended value of 2000 ms Defines the time to wait before retransmission of an APDU (application protocol data unit) segment.
Apdu Timeout milliseconds; defaults to recommended 3000 ms Defines the time to wait before retransmission of an APDU requiring acknowledgment, for which no acknowledgment has been received.
Location (optional) text string, defaults to unknown Describes the location of the BACnet device
Description (optional) text Describes the BACnet device object