You access this view by clicking, clicking the Configure button (
), and clicking the Alarm Classes tab.
Alarm classes categorize, group, and route alarms. The alarm class settings can provide alarm priorities and designate which alarms require acknowledgment. They are also the basis for visual grouping in the alarm console view.
In addition to the standard Filter and Export buttons, these buttons serve this view:
| Column/data item | Description |
|---|---|
| Display Name | Indicates the name associated with the activity. |
| Priority | Indicates the significance of the alarm. The lower this number the more significant the alarm. |
| Total Alarm Count | Indicates the total number of alarms. |
| Open Alarm Count | Indicates the total number of alarms that are currently open and unacknowledged. |
| In Alarm Count | Indicates the total number of alarms that are currently active. |
| Unacked Alarm Count | Indicates the total number of alarms that have not been acknowledged. |
| Time of Last Alarm | Reports when the most recent alarm was saved to the database. |