Activity Monitor Alarm Classes tab

In addition to the seven days of history records selected on the Activity Monitor tab, the Activity Monitor view displays alarm records for all assigned alarm classes. This tab provides a way to assign or unassign alarm classes for monitoring.
Figure 17.   Edit Activity Monitor view, Alarm Classes tab
Image

You access this view by clickingMonitoring > Activity Monitor, clicking the Configure button (Image), and clicking the Alarm Classes tab.

Alarm classes categorize, group, and route alarms. The alarm class settings can provide alarm priorities and designate which alarms require acknowledgment. They are also the basis for visual grouping in the alarm console view.

Control buttons

In addition to the standard Filter and Export buttons, these buttons serve this view:

  • Image Unassign removes the assignment.
  • Image Hyperlink links to the edit view or window for the selected item. It is the same as double-clicking the table row. This button is available when a single record is selected.
  • Image Assign Mode buttons open and close the Unassigned pane.

Activity Monitor columns

Column/data item Description
Display Name Indicates the name associated with the activity.
Priority Indicates the significance of the alarm. The lower this number the more significant the alarm.
Total Alarm Count Indicates the total number of alarms.
Open Alarm Count Indicates the total number of alarms that are currently open and unacknowledged.
In Alarm Count Indicates the total number of alarms that are currently active.
Unacked Alarm Count Indicates the total number of alarms that have not been acknowledged.
Time of Last Alarm Reports when the most recent alarm was saved to the database.