This tab opens when you click , and click the plus button (
).
In addition to the standard buttons (Delete, Filter and Export) these buttons support console recipient alarm classes:
| Column | Description |
|---|---|
| Display Name |
Reports the name that describes the event or function.
|
| Priority |
Reports the priority level assigned to the alarm class for each component state transition (from normal to
Offnormal, from normal to Fault, from offnormal, fault or alert to Normal, and from normal to Alert).The lower the number, the more significant the alarm. The highest priority alarm (most significant) is number 1.The lower
the number, the more significant the alarm. The highest priority alarm (most significant) is number 1.
|
| Total Alarm Count |
Displays the total number of alarms assigned to the alarm class from all sources.
|
| Open Alarm Count |
Displays the total number of current alarms. An alarm is considered to be open when it is not acknowledged and normal or not
acknowledged and in alarm.
|
| In Alarm Count |
Displays the total number of alarm sources.
|
| Unacked Alarm Count |
Displays the total number of unacknowledged alarms.
|
| Time of Last Alarm |
Reports the time that the system generated the last alarm assigned to this alarm class.
|