To access this view from the main menu of a remote host controller station, click .
In addition to the standard properties (Status, Fault Cause and Enabled), these properties support access control configuration.
| Property | Value | Description |
|---|---|---|
| Cache Status | read-only | Indicates if cache is currently being used. Caching speeds up access. If access is slow, check this property value to see if caching is currently inactive or failed. Cache is normally temporarily disabled during a join process. |
| Display Unknown Wiegand Formats | true or false (default)
|
Turns off (false) unknown Wiegand messaging. |
| Has Pin Duress | true or false (default)
|
Turns the PIN duress alarm feature on and off. |
| Pin Duress Offset | text | When PIN Duress is enabled, sets a number used for incriminating a PIN value to indicate duress. For example, if a PIN number
is 1234 and the Pin Duress Offset value is 2, a PIN number of 1236 causes a duress alarm if the Pin Duress Enabled property is set to true.
|
| Remote Validation | true or false (default)
|
Controls the validation of user credentials at a remote location. Remote validation usually takes less than five seconds.
However, if a Supervisor station is busy or has a large database, remote validation can take much longer, or may not be successful
at all. In this situation, a card holder may walk away prior to the door unlocking, creating a security risk. For these reasons,
this property defaults to false. If it is disabled on either the Supervisor or remote station, remote validation does not occur.
|