You access this view from the main menu by clicking , double-clicking the NrioNetwork row in the table, double-clicking a module, clicking the Point Manager button, followed by clicking the link to a specific point.
| Property | Value | Description |
|---|---|---|
| Facets | additional properties | Refer to Voltage Input points properties. |
| Proxy Ext | additional properties | Refer to Voltage Input points properties. |
| Out | read-only | Reports the current value of the proxy point and its status. |
| linearCalibration | additional properties | Refer to Voltage Input points properties. |
Facets determine how a point’s value displays in the station. Voltage Input facets include voltage numbers and decimal precision.

This Edit window opens when you click the Edit button.
| Property | Value | Description |
|---|---|---|
| Quantity | drop-down list | Defines input voltage. |
| max | number | Defines the maximum voltage value. |
| min | number | Defines the minimum voltage value. |
| precision | number | Defines the number of decimal places allowed. |
| units | defaults to Volts | Configures the default unit. |
These properties configure the proxy point extension.

In addition to the standard properties (Status, Fault Cause, andEnabled), these properties support the voltage proxy extension.
| Property | Value | Description |
|---|---|---|
| Conversion | Drop-down list (defaults to Default)
|
Defines how the system converts proxy extension units to parent point units.
NOTE: In most cases, the standard
Default conversion is best.
|
| Tuning Policy Name | drop-down list (defaults to Default Policy)
|
Selects a network tuning policy by name. This policy defines stale time and minimum and maximum update times. During polling, the system uses the tuning policy to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only |
Displays the last value read from the device, expressed in device facets.
|
| Write Value | read-only (applies to writable types only) |
Displays the last value written using device facets.
|
| Poll Frequency | drop-down list (defaults to Normal)
|
Selects among three rates (Fast, Normal and Slow) to determine how often to query the component for its value. The network’s
Poll Service or Poll Scheduler defines these rates in hours, minutes and seconds. For example:
This property applies to all proxy points. |
| Instance | number |
Defines the point’s I/O terminal address based on its hardware type.
If duplicated (same instance as same hardware type, same board), the point reports a fault status. If an edit attempt is made to an instance already in use by another proxy point, the system discards the edit, and retains the previous instance value. |
| Ui Type | read-only | Identifies the Nrio Universal Input point type: Resistive Input, Boolean Output, etc. |
These properties calibrate the calculated voltage value before it is applied to the Out slot, where [(calculatedValue x Scale)
+ Offset] = Out value. Usage is optional, although Offset and Units are commonly configured.
Units value in this extension to match the units in the point facets, otherwise the parent proxy point reports a fault for status!Typically, you see this fault status immediately after you add a new input point, for example a VoltageInputPoint or ResistanceInputPoint,
and configure it with a Linear conversion type (including a scale and offset), and then specify the point’s facets. It may
not be immediately clear that the problem is in this Linear Calibration Ext, where you must match its Units value to the units
in the point’s facets.

| Property | Value | Description |
|---|---|---|
| Scale | number, defaults to 1.0 | Defines a scale value. Usually you leave this value set to the default. One exception is if you copied this extension under a CounterInputPoint for the purpose of returning a scaled total. |
| Offset | positive or negative number, defaults to 0.0 | Can compensate for signal error introduced by sensor wiring resistance. If under a CounterInputPoint, leave it at zero (0). |
| Units | drop-down list | Defines the unit of measure. Should be the same as the parent proxy point’s facets. |
| Fault Cause | read-only |
Indicates the reason why a system object (network, device, component, extension, etc.) is not working (in fault). This property
is empty unless a fault exists.
|