Alarm Relay tab

Each input may have one or more alarm relay devices assigned to it. This allows you to choose an alarm extension assignment on an input, as you would do with a Relay Out.

Properties

Property Value Description
Status read-only
Reports the condition of the entity or process at last polling.

{ok} indicates that the component is licensed and polling successfully.

{down} indicates that the last check was unsuccessful, perhaps because of an incorrect property, or possibly loss of network connection.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem. Refer to Fault Cause for more information.

Relay Out Ref Chooser Defines which output this relay is connected to. The system automatically populates the Ref Chooser with the available outputs.
Assignment Ref Chooser Defines which input this relay is connected to. The system automatically populates the Ref Chooser with the available inputs.
Relay Type drop-down list
Defines how the relay out behaves relative to the assigned input. You can toggle relay settings on and off or the relay may be out of phase (inverse) with the assigned input.

Follow matches the state of the assigned input.

Inverse selects the relay out status that is the opposite of the assigned input state.

Toggle on active changes the relay from its current state when the assigned input state changes to active.

Toggle on inactive changes the relay from its current state when the assigned input state changes to inactive.

Inverse   Sets the relay out state to the opposite of the assigned input state.
Toggle On Active   Changes the relay out status from its current state when the assigned input state changes to inactive.