IP Port tab

This tab configures the BACnet/IP link layer used by the controller, providing that the Enabled property (in BACnet Network tab) is set to true.
Figure 195.   IP Port tab
Image

To access this view, click Controller Setup > Remote Devices > BACnetNetwork, followed by clicking the IP Port tab.

Properties

In addition to the standard properties (Enabled, Status, and Fault Cause) these properties support the BACnet IP Port.

Property Value Description
Network Number number from 1 to 65534; default value is -1 (inoperative) Specifies a unique network number across the entire BACnet internetwork for the BACnet/IP network.
Adapter drop-down list (defaults to NET1) Specifies which of the two physical Ethernet ports on the controller is used for BACnet/IP communications.

NET1 or NET2

UDP Port port number (defaults to 0xBAC0, decimal 47808) Specifies the UDP (user datagram protocol) port used by BACnet/IP. You can specify another port, if needed (say an existing BACnet/IP network is using another UDP software port).
IP Device Type drop-down list: (defaults to BACnet device) Defines the type of BACnet/IP device Generally, the default Standard should by used.

BACnet device

BBMD (BACnet Broadcast Management Device)

BACnet Foreign Device

Bbmd Address number (defaults to null) Sets the Bbmd (BACnet Broadcast Management Device) address. This address is only required when the system is being used as a BACnet Broadcast Management Device.