This window opens from the main menu when you click , followed by selecting an alarm history record and clicking the Filter button (
)
| Criterion | Value | Description |
|---|---|---|
| Alarm Time | drop-down list | Selects the period of time to include in the report. To further filter report records based on alarm time, refer to a topic titled “Advanced Time Range Options window.” |
| Normal Time | drop-down list and Ref Chooser | Selects a time range for reporting alarms that returned to normal. To further filter report records based on normal time, refer to a topic titled “Advanced Time Range Options window.” |
| Source Name | wild card (%) | Selects alarms to include based on the component ORD. |
| Alarm Class | wild card (%) | Selects alarms based on alarm class. Alarm class defines alarm routing. |
| Source State | Enum chooser | Selects an alarm state: Normal, Offnormal, Fault and Alert. |
| Ack State | Enum chooser | Selects the state of the acknowledgment: Acked (acknowledged), Unacked (unacknowledged) and Act Pending (about to be acknowledged). |
| Priority | number | Selects alarms to display based their priority from 1 to 150, where 1 is the highest priority. |
| Message | wild card (%) | Selects alarms to display based on the message associated with the alarm. |
| Badge | wild card (%) | Selects alarms to display based on the badge number of a person. |
| User | wild card (%) | Selects alarms to display based on the user who was logged in when the system generated the alarm. |