Prerequisites:
Workbench is open with network access to both the
Niagara Enterprise Security system and the building control stations.
- In the station, navigate to and expand the module, points, door and reader that you are using for access integration (from a Supervisor station, perform
point discovery, if necessary).
- Last Location Id contains the integration ID value of the last badge that was presented at the reader.
- Valid Badge has a Boolean value output that provides a two-second (default) pulse when a valid badge is presented.
- Using the Last Location Id and Valid Badge points as inputs, create logic on a
Workbench wire sheet that requires both of the following to be
true:
- Last Location Id (lastLocationId) value must equal the value of the targeted location. Multiple locations can be defined as a group with a
single value. This is the value that the integration ID from the access right must match.
- Valid Badge (validBadge) value must be set to
true. The badge-holder must be authorized as having access at the targeted building door.
The combination of these two pieces of information indicate that an authorized person entered the space and the occupation
area associated with the person. The following simple wiresheet illustration provides an example of logic that could be used
to turn on lighting when an authorized person gains access to an area.