Routing intrusion zone alarms to the Supervisor

This procedure configures the system to send intrusion zones alarms to the Supervisor station.
Prerequisites: You have created the intrusion zone in the controller station.
  1. In the controller station, click Controller Setup > Intrusion Setup > Intrusion Zones, double-click the zone, click the Points tab, and click the Assign Mode button (Image).
    The Unassigned pane lists the available points.
  2. Add the points in the controller station for the intrusion zone.
  3. Click the Grouping tab and click the Assign Mode button (Image).
    The Unassigned pane lists the available Supervisor stations.
  4. Select the Supervisor station in the Unassigned pane, click the Assign button (Image), and click Save.
  5. Click the Recipients tab and click the Assign Mode button (Image).
    The Unassigned pane lists the available alarm recipients.
  6. Select the Supervisor as the alarm recipient, click the Assign button (Image), and click Save.
  7. Connect to the Supervisor station, click System Setup > Remote Devices > Station Manager, and click the Replicate button.
    You can now view the intrusion zone in the Supervisor as well as the remote controller station.
  8. In the Supervisor station, click System Setup > Intrusion Setup > Intrusion Zones, click the Add button (Image), click the Recipients tab, and click the Assign Mode button (Image).
    The Unassigned pane opens with the list of available alarm recipients.
  9. Select the Console Recipient or other applicable recipient, click the Assign button (Image), and click Save.