Motion, glass break, and auxiliary door sensors

The following properties provide examples of how to configure individual sensors.

Motion detector

Tab Property Value
Configuration Facets trueText=active, falseText=inactive
Enabled true
Inactive State Closed
Alarm Setup Alarm Settings Alarm Class High Priority
Active Alarm Message Motion detected office
Return to Normal Message No motion
Alarm Inhibit Schedule Business Hours (or the equivalent)
Supervisor Fault Alarm Class High Priority

Glass break sensor

Tab Property Value
Configuration Facets trueText=active, falseText=inactive
Enabled true
Inactive State Closed
Alarm Setup Alarm Settings Alarm Class High Priority
Active Alarm Message Broken window office
Return to Normal Message none
Alarm Inhibit Schedule none
Supervisor Fault Alarm Class High Priority

Auxiliary door sensor

Tab Property Value
Configuration Facets trueText=active, falseText=inactive
Enabled true
Inactive State Closed
Alarm Setup Alarm Settings Alarm Class High Priority
Active Alarm Message Auxiliary door open
Return to Normal Message Auxiliary door shut
Alarm Inhibit Schedule none
Supervisor Fault Alarm Class High Priority