This procedure documents logging in to a controller station for the first time or after upgrading software.
Prerequisites: The station has been commissioned and is running. You are using the web UI.
- Open a supported web browser.
- In the address bar, type the address of the remote controller (the default IP address is:
https://192.168.1.120) and press the Enter.The Login window opens. The Username defaults to admin. The password defaults to Admin12345.
- Do one of the following:
- If you are logging in to this station for the first time, and did not connect to the station using
Workbench, enter the factory default
Password, if enabled, disable Remember these credentials, and click OK.
- If you already logged in to the station using
Workbench and changed the password, enter your password.
If you entered the default password, the system displays the Password Reset window.
- Change the default password to a new, strong password that includes special characters, numbers, and lowercase and uppercase
letters.
IMPORTANT: The password provides the front line of protection for your controller station. Share this credential with only those who
need to know. Change the password on a regular basis. Store it in a secure location, preferably under lock and key.
Once you have created your own unique password, the next time you log in to the station you can enable Remember these credentials before you click OK.
The interface opens and you are asked to confirm the station and system display name and the network settings.
The Station and System names display in the top right corner of the web UI. For example: the station name might be: Second Floor, and the system name: Building 10. You can change these values later by navigating to . The Reference explains the many properties you can configure in this view.
- Scroll down and configure any of the many properties, then click Apply Changes and Reboot (at the bottom of the page), and wait for the station to restart.
If the station does not restart, go back to
Workbench, confirm that Auto-Start is enabled, click Start, and log in using the web UI again.
- If the Guided Setup Tour does not open, and you wish to use it, click the Guide button at the top of the Home view.
The Guided Setup Tour window opens.