| Base Reader Module.Di2, Di3 |
These are digital inputs that are mapped to different doors, which give the access based on the badge validity. |
| Base Reader Module.Door 1.Exit Request |
If the door has an exit request device, This field allows you to designate the supervised input that is used for the request
to exit sensor.
|
| Base Reader Module.Door 1.Sensor |
If the door has a sensor device, use an option list to designate the supervised input that is used for the door sensor. Sensor
is mainly used to specify door is Locked or Unlocked.
|
| IntrusionTimeoutExt |
An alarm event that occurs if the intrusion zone is armed and the door sensor changes to true after access is granted and
the intrusion zone is not disarmed before the countdown expires. The extension must be edited as an Entry Point. If the zone
is disarmed before the countdown expires, the countdown ends and the alarm is inhibited. This allows for annunciation that
the zone is armed.
|