Configuring the intrusion display

These AlarmService properties control what appears on the display.
Prerequisites: You are working in Workbench connected to your station that manages the intrusion zones.
  1. Expand Config > Services > AlarmService
  2. Double-click the AndroidIntrusionDisplay node.
    The intrusion display’s AX Property Sheet opens.
    Image
  3. Set up the Default Message.
    This message displays when Default Page is set to Time. This page displays after a period of inactivity.
    Image
    1. Default Message
    2. Default Page
  4. Select Summary from the drop-down list for Default Page.
    This page displays under the Default Message on the default screen. It can display the current time or the state of the intrusion zone(s) that are associated with the display. If your display is in a public area, you may not want to use the summary page as your default.
    Image
    1. Default Page
  5. If a PIN is required to arm the system, set Arming Pin Required to true.
    A PIN is always required to disarm the system.
  6. If a PIN is required to view the status of the system, set Status Pin Required to true.
  7. Select a value for Point Display.
    Normal Path displays the station path to a point that is in alarm when performing an arming test or arm-with-time-delay-system. If the point exists in another station, the path displayed points to the remote station, for example: entSecurity801.Input/Output Module.Sdi1. If the point is in the local station, this property outputs None.

    Displays the Station Path to a Point: displays the path to a point starting with the point reference when doing an arming test or arm-with-time-delay-system. For example: Sdi1.Input/Output Module.entSecurity801

    None: displays the local station path to a point that is in alarm when doing an arming test or arm-with-time-delay-system. For example, entSecurity801.Input/Output Module.Sdi1