Readers cause doors to open or remain closed based on scanning the information presented to the reader on a badge. They provide
the information the Personnel department needs to tract attendance.
Prerequisites: A door has an electric door strike, a sensor with alarm notification, and entry and exit readers with no keypads.
The door’s request to exit shunts alarms only. It does not unlock.
Perform the following steps:
- Navigate to .
- Double-click the module to which the door and its reader are connected.
The Remote Reader Module tab opens.
- Click the Doors tab and click the door’s hyperlink.
The Doors tab opens.
- Configure the Strike, Sensor, and Exit Request tabs as follows and click Save.
| Tab |
Property |
Value |
| Strike |
Locked State |
Open |
Auto Relock |
Relock On Door Open |
Schedule Operation |
Normal |
Unlock Schedule |
None |
Override Schedule |
None |
Door Lock Output |
Relay Output 1 (depends on your configuration)
|
| Sensor |
Closed State |
Closed |
Door Held Open Limit |
30 Sec |
Door Forced Alarm Class |
High |
Door Held Open Alarm Class |
Medium |
Sensor Fault Alarm Class |
High |
Sensor Input |
Supervised Digital Input 1 (depends on your configuration)
|
| Exit Request |
Inactive State |
Open |
Enabled Schedule |
None When no schedule is assigned, the system enables a request-to-edit by default.
|
Unlock On Exit Request |
No |
Exit Request Fault Alarm Class |
High |
Request-to-Exit Input |
Supervised digital Input 2 (depends on your configuration)
|
- To give an existing reader a more descriptive name, click Manage Devices, select
Rename and click Ok, select the reader and click Ok, type in a name and click Ok.
- To add a reader, click Manage Devices, select
Add and click Ok, select a reader and click Ok, type in a name and click Ok.To add a reader, you must have already installed the hardware.
- Click the entry reader’s hyperlink, configure its properties, then click the exit reader’s hyperlink and configure its properties.
Click Save after configuring each set of properties.
| Tab |
Property |
Value |
| Reader |
Enabled |
true |
Reader Config |
Reader Only |
Time Attend |
Clock In for the entry reader and Clock Out for the exit reader
|
Assignment |
(defaults to name of the door) |
| Activity Alerts Exts |
for all alarms: Alarm Class |
Medium |
for all alarms: Enable Logging |
(selected) |
| Output Configuration |
Valid Green |
Follow Strike State |
Green Inactive State |
Open |
Red Inactive State |
Closed |
Valid Beeper |
Custom Time, On 1 Sec
|
Invalid Beeper |
Custom time, On 2 Sec
|
Beeper Inactive State |
Open |
Beeper on Door Held Open Alarm |
Warning Only with warning time: 15 seconds before the door-held-open alarm sounds. Activating the beeper-on-door-held-open alarm reminds
employees to shut the door, saving energy and preventing anything else from entering the building.
|