Configuring a door with an electric strike mechanism

This procedure configures a typical door mechanism that locks upon a loss of power.
Prerequisites: The door to configure has a card reader with no keypad, a fail-secure electric door strike, a door sensor with alarm notification and a request to exit for shunt alarms only; it does not unlock. A schedule indicating when the door is unlocked (for normal business hours) exists.
Perform the following steps:
  1. Navigate to Controller Setup > Remote Devices > Remote Modules > Remote Module Setup.
  2. Double-click the module to which the door and its reader are connected.
    The Remote Reader Module tab opens.
  3. To associate the reader with the door, set Enabled to true and click the Doors tab.
    The Doors tab opens.
  4. To give the door(s) more descriptive names, click Manage Devices, select Rename and click Ok, select the door and click Ok, type in a name and click Ok.
  5. Click the hyperlink to the door view.
    The Readers tab opens.
  6. To give the reader a more descriptive name, click Manage Devices, select Rename and click Ok, select the reader and click Ok, type in a name and click Ok.
  7. Click the Strike tab and configure its properties according to the screen capture using the company’s Unlock Schedule.
    Image

    Schedule Operation requires a schedule so that the system can identify the first validation, which triggers unlocking the door.

    The Door Lock Output value depends on the hardware configuration.

  8. Click the Sensor tab and configure the properties according to the screen capture.
    Image

    The Sensor Input value depends on the hardware configuration.

  9. Click the Exit Request tab and configure the properties according to the screen capture.
    Image

    The Request-to-Exit value depends on the hardware configuration.

  10. To save the configuration, click Save and test the door.