Another New dialog box appears.

Note the following about entries in the Add dialog box:
NameThis property is the unique point name. This is the
TypeIt is the
Object IdentifierBecause the Snmp proxy points are not “discovered” when you use the New button, the OID values must be typed in manually.
Variable TypeThis property specifies the type of the value written out to the SnmpDevice at the location of the OID specified in the Object Identifier property. This property is usually automatically set when the Snmp proxy point is automatically created but must be typed in when creating the proxy point manually.
EnabledThis property allows you to set the proxy point in service (with a true value) or to set it out of service (with a false value).
Device FacetsThis property represents the device proxy point facets that affect how the value should be displayed in
FacetsThis property represents the parent proxy point’s facets that affect how the value should be displayed in
ConversionThis property specifies the conversion to use between the “read value” (in Device Facets) and the parent point facets, where “Default” is typically used.
Tuning Policy NameThis property specifies the Snmp service type to use when binding to this item.
The points are added to the station, and appear listed in the Database pane of the Snmp Point Manager view.