To access one of these views, double-click the component node in the Nav tree or right-click the component and click .
Modbus Client Point Manager offers no learn mode. The protocol’s simplicity makes these functions unnecessary. Instead, you use the New button to create proxy points, referring to the vendor’s documentation for the addresses of data items in each Modbus device.
By default, only a few of the available columns in the Modbus Client Point Manager are enabled for display, notably Name, Out and Absolute Address. However, you may wish to change this by clicking on the Table Options menu in the table’s upper right. For example, during the configuration process you may wish to see Fault Cause and Data Source.
| Column | Description |
|---|---|
| Path | Displays the ord path of point. |
| Name | Displays the name of point. |
| Type | Indicates the type of point. |
| Out | Reports the current out value, including any point facets. This defaults to the single (configured) property value along with status for the proxy point. |
| Enabled | Reports if the proxy point is currently enabled for communication. |
| Tuning Policy Name | Displays the name of the tuning policy |
| Absolute Address | Displays the actual address that uses when polling for this discrete data point from the actual Modbus device. |
| Fault Cause | Indicates the condition at the last check. |
| Poll Frequency | Displays the poll services that is used in the device. |
| Data Address | Displays the address of the polled data item |
| Reg Type | Displays the register type. |
| Data Type | Displays the location of data. |
| Status Type | Displays the location of points. |
| Bit Number | Displays the bit number. |
| Beginning Bit | Displays the bit in the register. |
| Number of Bits | Displays the number of bits used for point. |
| Data Source | Displays the data source. |
| Number Registers | Displays the number of consecutive holding registers to read. |
| Device Facets | Represents the facets learned from the point. |
| Facets | Displays the facet value. |
| Conversion | Displays the units to use when converting values from the device facets to point facets. |
| Read Value | Displays the value read by the driver. |
| Write Value | Displays the value to be written. |
| Button | Description |
|---|---|
| New Folder | Adds new folder in the Modbus Network |
| New | Adds a new device |
| Edit | Edits the added devices |