Duplicate.Input Register Base Address, Holding Register Base Address, Coil Status Base Address, and Input Status Base Address).All base address properties of a device default to hexadecimal zero (hex: 0). However, you can use them as an engineering method (along with multiple device objects) to quickly configure unique proxy point addresses. This works when a Modbus device has data partitioned into multiple areas with repeating address patterns. This way, the same device (and child proxy points) can be replicated, and the only address changes made in the base address.
Hex or Decimal for the Address Format.Modbus for the base address and child proxy point addresses.
Address.Holding Register Base Address is set to Decimal, and its Address is set to 100, each child Modbus proxy point that has a holding register Address Format of Decimal, and an Address of 13 is effectively addressed as Decimal, 113 (Absolute Address).