Configuring Ethernet properties

Ethernet properties include the gateway’s IP address and port. These properties apply to the ModbusTcpNetwork, ModbusTcpGateway, and ModbusTcpSlaveNetwork components.
Prerequisites: The network exists in the Nav tree.
  1. If you have not already done so, navigate to the network node, right-click it and click Views > Property sheet.
    The Property Sheet opens.
  2. In the Ip Address property, enter the Modbus gateway’s unique IP address, replace the ###.###.###.### with the IP address.
    Each ModbusTcpDevice you add under a ModbusTcpNetwork requires the IP address used by that device. Usually, each Modbus TCP device uses this address (only) for communications with its Modbus address (1-247) often left at 1.
  3. In the Port property, review the default 502 value and change this port identifier as needed.
    This is the standard port used by Modbus TCP.
  4. While this network’s property sheet is open, review its global Modbus settings.
  5. Click the Save button.