Logger Configuration view (workbench-LoggerConfiguration)
This view configures the log level of station processes. This tunes the station output seen in the Application Director.

To access this view, expand and double-click DebugService.
In the example shown above, the Log Category (1) of the bacnet.client process (2) is being added with a log level of FINE (3). Clicking the add icon (4) adds the filter to the Configured Log Categories list and clicking Save (5) completes the task. Such an entry might be useful to troubleshoot errors about writes to BACnet proxy points.