To access this view, expand , double-click SnmpAgentBooleanPoint.
In addition to the standard properties (Status, Enabled and Fault Cause), these properties are unique to this component.
| Property | Value | Description |
|---|---|---|
| Facets | read-only | Determine how values are formatted for display depending on the context and the type of data. For example, instead of the
Boolean facets trueText and falseText you may want to display ON and OFF, Access Granted and Access Denied or Locked and Unlocked.
You access facets by clicking an Edit button or a chevron >>. Both open an Edit Facets window. |
| Device Facets | additional properties | Configures additional parameters for the device proxy point facets for how the value should be displayed in Niagara. Please confirm. |
| Conversion | drop-down list | Defines how the system converts proxy extension units to parent point units.
NOTE: In most cases, the standard
Default conversion is best.
|
| Tuning Policy Name | drop-down list | Configures network rules for evaluating both write requests to writable proxy points as well as the acceptable freshness of read requests. |
| Read Value | read-only | Displays the last value read from the device, expressed in device facets. |
| Write Value | read-only | Displays the last value written, using device facets. |
| Object Identifier | read-only | Displays the full OID to use for accessing the data value for this point from the Input Table (or Output Table) by an outside Snmp manager. Snmp GET or SET requests would use this full OID to access the value of the proxy point. |
| Index | number | Need Information |
| Out | read-only | Represents the point slot that contains the value to output. |
| Override Expiration | read-only | Reports how long a value that has been set manually (using an action) remains valid. |
| Min Active Time | hours minutes seconds (defaults to 00000h 00m 00s) |
Defines a minimum up time. This property works independently of Min Inactive Time. You typically use this property to prevent the short-cycling of equipment controlled by the point. The default disables the timer. |
| Min Inactive Time | hours minutes seconds (defaults to 00000h 00m 00s) |
Defines a minimum down time. This property works independently of Min Active Time. You typically use this property to prevent the short-cycling of equipment controlled by the point. The default disables the timer. |
| Set Min Active Time on Start | true or false (default) |
Determines if the minimum inactive time applies at station start. |