Prerequisites: Workbench should be running.
Perform the following steps:
- In workbench, open the tls palette.
- Add the following ReadPoints folder from the palette.
- Expand ReadPoints in the palette and drag the Tls350PriAlmHis component, under the Points container of the Tls350ConsoleDevice.
- Add the below points, under the Points container of the Tls350FuelTankDevice.
- Tls350InTankSta
- Tls350InTankInv
- Tls350BirAdjDel
- Open the Property Sheet for Proxy Ext for each of the added points, set the following property and perform to actions.
Minimum Poll Interval:
- Alarms and status should be 30 seconds, 1 minute and 60 minutes or based on requirements. And 0 results means no poll.
- Inventory and delivery should be 15 minutes, 30 minutes, 60 minutes, or based on requirements. And 0 results means no poll.
- Actions
- Read Data: Performs an immediate poll.
- Clear Data : Clears retained data that prevents recording polled events multiple times (use when data also cleared from Veeder-Root controller,
so that JACE resources are occasionally freed up).
- Clear Logs : Clears any linked Niagara histories.