Network

The Network container under BacnetComm determines the BACnet network-layer configuration for the station. You access BacnetComm directly in the Nav tree.
Figure 84.   BACnet network properties
Image
Property Value Description
Router Table    
Ip Port   See Network properties, Ip Port.
Routing Enabled true (default) or false  
Maintain Routing Enabled true or false (default)  
Minimum router Update time milliseconds (default: 500)  
Router Discovery Timeout milliseconds (default: 5000)  
Termination Time Value seconds (default: 120)  
MstpPort    

Network properties, Ip Port

Property Value Description
Network Number number (defaults to 1)  
Link container for additional properties B/IP (none:0xBAC0) Standard
Link, Adapter drop-down list  
Link, Ip Address text (defaults to none)  
Link, Udp Port 0xBAC0 Bbmd Address
Link, Ip Device Type drop-down list  
Link, Bbmd Address null  
Link, Registration Lifetime hours minutes seconds  
Link, Broadcase Distribution Table BDT: 0 entries  
Link, Foreign Device Table    
Link, Bbmd Debug true or false (default)  
Status read-only
Reports the condition of the entity or process at last polling.

{ok} indicates that the component is licensed and polling successfully.

{down} indicates that the last check was unsuccessful, perhaps because of an incorrect property, or possibly loss of network connection.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem. Refer to Fault Cause for more information.

Fault Cause read-only
Indicates the reason why a system object (network, device, component, extension, etc.) is not working (in fault). This property is empty unless a fault exists.
Poll Service additional properties
Configures the frequency with which the driver polls points and devices.

“Poll Service properties” in the Niagara Drivers Guide documents these properties.

Max Devices max  
Enabled true or false
Activates (true) and deactivates (false) use of the object (network, device, point, component, table, schedule, descriptor, etc.).
Port Id read-only
Reports the number of the Ethernet port you are configuring.
Port Info read-only
Reports the type of port (Ethernet, MS/TP, etc.).

Network properties, Ip Port, Poll Service

Property Value Description
Poll enabled true (default) or false  
Fast Rate hours minutes seconds  
Normal Rate hours minutes seconds  
Slow Rate hours minutes seconds  
Statistics Start null  
Average Poll    
Busy Time    
Total Polls    
Dibs Polls    
Fast Polls    
Normal Polls    
Slow Polls    
Dibs count    
Fast Count    
Normal count    
Slow Count    
Fast Cycle Time    
Normal Cycle Time    
Slow Cycle Time    

Network properties, MstpPort

Property Value Description
Network Number number (default: –1)  
Link MAC 0 on COM1 at Baud_9600  
Link, Port Name COM1  
Link, Baud Rate drop-down list (default: Baud_9600)  
Link, Mstp Address 0–127 (default: 0)  
Link, Max Master 0–127 (default: 127)  
Link, Max Info Frames 0–100 (default: 20)  
Link, Support Extended Frames true or false (default)  
Status read-only
Reports the condition of the entity or process at last polling.

{ok} indicates that the component is licensed and polling successfully.

{down} indicates that the last check was unsuccessful, perhaps because of an incorrect property, or possibly loss of network connection.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem. Refer to Fault Cause for more information.

Fault Cause read-only
Indicates the reason why a system object (network, device, component, extension, etc.) is not working (in fault). This property is empty unless a fault exists.
Poll Service  
Configures the frequency with which the driver polls points and devices.

“Poll Service properties” in the Niagara Drivers Guide documents these properties.

Max Devices max  
Enabled true or false
Activates (true) and deactivates (false) use of the object (network, device, point, component, table, schedule, descriptor, etc.).
Port Id read-only
Reports the number of the Ethernet port you are configuring.
Port Info read-only
Reports the type of port (Ethernet, MS/TP, etc.).