Null On Inactive property is also available. Default action is Direct (cooling).
Tstat is available in the HVAC folder of the kitControl palette.

| Property | Value | Description |
|---|---|---|
| Facets | Config Facets window (defaults to true and false) | This configuration applies to the Out property value.
|
| Out | read-only StatusBoolean true and false |
Displays the result of the calculation. |
| Null On Inactive | true or false (default)
|
true sets the Out value to null when the component is inactive.
|
| Cv | number (defaults to null) and null definition | Defines an input Control Variable (Cv).
When null is checked, the value displayed defaults to the incoming value from the device.If you remove the check mark you
can configure the |
| Sp | number (defaults to null) and null definition | Defines the input thermostat Setpoint (Sp).
When null is checked, the corresponding value defines the default when a calculation returns null. |
| Dif | number (defaults to null) and null definition | Defines an input differential (Dif).
When null is checked, the value displayed defaults to the incoming value from the device.If you remove the check mark you
can configure the |
| Action | drop-down list | Direct performs the calculation directly on the input variables.
|
| Null On In Control | true (default) or false |
true sets an In value to null.
|