StatusStringToStatusNumeric is available in the Conversion folder of the kitControl palette.
The input string must contain only numeral characters, and optionally one period (.) for decimal notation. Valid input strings examples are 145678 or 34.81. Leading and/or trailing space characters are allowed and ignored. Any other input string characters (for example, alpha, punctuation) result in a fault status.

| Property | Value | Description |
|---|---|---|
| Facets | Config Facets window (defaults to null for units and one decimal place of precision) |
Selects unit and configures how the value displays:
In property value.
|
| Out | read-only number | Displays the converted target status numeric value. |
| In | number and null definition (defaults to 0) | Displays the source status text.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| On Null In Value | drop-down list (defaults to Use In Value) | Configures how to handle null values.
If this modified component links to another StatusString property, the framework ignores the null value. But, if connected to a StatusStringToStatusNumeric component, the result of a null input value defaults to the changed value, which may not be what you intended.
|
| Out Value On Null | number | Defines an In value for the conversion object when its Out value has a null status.
|