kitControl-StatusDemux

This component provides a method to check for individual status flags of the In-linked object, and sets corresponding (demuxed) StatusBoolean out slots active (true) if that status as found.

StatusDemux is available in the Util folder of the kitControl palette.

Figure 128.   StatusDemux properties
Image
Property Value Description
In Status check boxes Identifies the possible conditions of the In-linked object: disabled, fault, down, alarm, stale, overridden, null and unackedAlarm.
In Boolean true or false (default) and null definition Receives input from a connected Boolean object.
In Enum enumerated value (defaults to zero) and null definition Receives input from a connected Enum object.
In Numeric number (defaults to zero) and null definition Receives input from a connected Numeric object.
In String text (defaults to blank) and null definition Receives input from a connected String object.
Alarm out property: true or false (default) and null definition Activates (true) if the In-linked object is in alarm.
Down out property: true or false (default) and null definition Activates (true) if the In-linked object is down.
Fault out property: true or false (default) and null definition Activates (true) if the In-linked object is in fault.
Null Status out property: true or false (default) and null definition Activates (true) if the In-linked object is in null status.
Disabled out property: true or false (default) and null definition Activates (true) if the In-linked object reports a disabled.
Overridden out property: true or false (default) and null definition Activates (true) if the In-linked object has been overridden.
Unacked Alarm out property: true or false (default) and null definition Activates (true) if the In-linked object has an unacknowledged alarm
Stale out property: true or false (default) and null definition Activates (true) if the In-linked object is stale (has not been updated in a timely manner).