Purge Enabled input is true.
NightPurge is available in Energy folder of the kitControl palette.
For inside and outside comparisons, you can select either temperature or enthalpy comparisons. There is also a low temperature check to protect against freezing.

| Property | Value | Description |
|---|---|---|
| Temperature Facets | Config Facets window |
Selects units and configures how the value displays:
Outside Temp, Inside Temp, and Low Temperature Limit property values.
|
| Humidity Facets | Config Facets window |
Selects units and configures how the value displays:
This configuration applies to the |
| Purge Enabled | StatusBoolean true or false (default) and null definition
|
true enables the night purge operation.
Often this slot is linked to a Not object sourced from a BooleanSchedule output. When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Outside Temp | number of degrees of temperature (defaults to 0.0F) and null definition | Defines the current outside air temperature. This input must be valid for this object to function.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Outside Humidity | percentage of relative humidity (defaults to 0.0 %RH) and null definition | Defines the current outside air humidity. This input must be valid for this object to function.
When null is checked, the corresponding value defines the default when a calculation returns null. |
| Inside Temp | number of degrees of temperature (defaults to 0.0F) and null definition | Defines the current inside air temperature. This input must be valid for this object to function.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Inside Humidity | percentage of relative humidity (defaults to 0.0 %RH) and null definition | Defines the current inside air humidity. This input must be valid for this object to function.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Low Temperature Limit | number of degrees of temperature (defaults to 0.0F) and null definition | Provides freeze protection.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Night Setpoint | number of degrees of temperatur (defaults to 0.0F) and null definition | Defines the night temperature setpoint, at or below which free cooling is not applied. Instead, the Current Mode is set to Satisfied.
When null is checked, the value displayed defaults to the incoming value from the device. If you remove the check mark you
can configure the |
| Outside Enthalpy | read-only energy measured in BTUs per pound to two decimal places (defaults to 0.00 BTU/lb) | Displays the calculated outside air enthalpy. |
| Inside Enthalpy | read-only energy measured in BTUs per pound to two decimal places (defaults to 0.00 BTU/lb) | Displays the calculated inside air enthalpy. |
| Free Cooling [output] | read-only StatusBoolean true or false (default)
|
Displays the value of the Free Cooling Command when free cooling should be used. Otherwise, it displays the opposite state, or null (if Use Null Output is set to true).
The component sets the |
| Current Mode | read-only value (defaults to Disabled |
Indicates which of the following modes this object is currently in:
|
| Setpoint Deadband | degrees of temperature to a single decimal place (defaults to 1.0F) | Applies temperature Setpoint Deadband when inside temperature falls below Night Setpoint before free cooling can be enabled.
|
| Threshold Span | number to two decimal places (defaults to 1.0) | Defines a value. The difference between the Inside Enthalpy and the Outside Enthalpy must be greater than this value before the component enables free cooling.
|
| Use Enthalpy | StatusBoolean true (default) or false |
true enables the use of enthalpy to determine if free cooling is available.
|
| Free Cooling Command | StatusBoolean true (default) or false |
Configures Free Cooling output.
|
| Use Null Output | StatusBoolean true (default) or false |
Configures Free Cooling output.
|