InA.
The Reset component is located in the Math folder of the kitControl palette.

When the outside air temperature is 0° F, the hot water setpoint is 200° F. When the outside air temperature is 75° F, the hot water setpoint is 100° F. The Reset object is configured as:
If the InA value is beyond the input limits, the output is limited by the corresponding output limit (in this case, 200 at 0° F or below,
100 at 75° F or above). When the input is at an intermediate value, the output scales linearly. For example, when the outside
air temperature is at 38.2° F, the Reset output is 149.1° F.