UserService (baja-UserService)
This service manages all system users: human and machine. You access it by right-clicking UserService and clicking .
The User Manager is the primary view of this service. By default, creating a new station using the New Station wizard includes the UserService. The baja module makes this service available.

To access these properties, expand , right-click UserService and click .
| Property | Value | Description |
|---|---|---|
| Lock Out Enabled | true or false | |
| Lock Out Period | true or false | |
| Max Bad Logins Before Lock Out | Number from 1–10 (defaults to 5) | |
| Lock Out Window | hours minutes seconds (defaults to 30 seconds) | |
| Default Auto Logoff Period | 0000h 15m (default) | Specifies the amount of time that a period of inactivity may last before a station connection is automatically disconnected. The acceptable range of values is two minutes to four hours. This limit is observed only when the User’s Use Default Auto Logoff Period property is set to true. |
| Absolute Logoff Enabled | true (default) or false | If enabled, the Absolute Logoff Enabled property is added to the User Manager view where it can be applied to individual users (as of Niagara 4.15). |
| Default Absolute Logoff Period | Number from 15min to 365 days (defaults to 7 days) | Specifies the amount of absolute time regardless of user activity or inactivity before a station connection is automatically disconnected. This limit is observed only when the user's Absolute Logoff Enabled property is set to true. |
| SMA Notification Settings | multiple properties | Configures the SMA (Software Maintenance Agreement) whose properties are documented in baja-SMANotificationSettings, which is in the document. |
| User Prototypes | multiple properties | Serves as a container for the default and other user prototypes whose properties are documented in baja-UserPrototypes, which is in the document. |