Alarm Portal
Alarm Portal options allow you to customize both the appearance and behavior of the Portal Alarm Console.

Alarm Portal options include the following:
| Property | Value | Description |
|---|---|---|
| Tray Icon Enabled | true (default) or false | Controls the display of an alarm icon. true enables the display of an alarm icon in the system tray when the alarm portal is active. false disables the display of an alarm icon in the system tray. |
| Alarm Popup Enabled | true (default) or false | Controls the display of an alarm popup window. true displays an alarm popup window when the alarm portal is active. false does not display this window. |
| Alarm Popup Always On Top | true (default) or false | Controls the location of the alarm popup window. Causes the alarm popup window to stay on top of other windows when the alarm portal is active, if set to true. |
| Alarm Popup Uncloseable | true (defauls) or false | Controls if an operator can close the alarm popup window. true makes the alarm popup window uncloseable when the alarm portal is active. false allows the alarm console to be closed. |
| Kiosk Mode | true or false (default) | Configures the use of kiosk mode for the alarm console. true configures the alarm console to open in kiosk mode the next time it starts. false maintains the standard mode. For related information, refer to the NiagaraAX Graphics Guide, |
| Reconnect Interval | hours, minutes, seconds | Defines when to attempt to reconnect a disconnected alarm console. If a console is disconnected, the framework attempts a reconnect within this interval. |
| Default Time Range | time range | Selects the default time range that displays in the Portal Alarm Console pane of the Alarm Console view (Console). |