You can configure how alarms appear in the Alarm
Console, acknowledge alarms and manage the database of
alarms. This topic summarizes in steps the basic ways to manage alarms.
You are working in Workbench and are connected to a station.
- To set up an alarm recipient, which is required to view
the Alarm Console, open the alarm palette, expand Recipients and add a ConsoleRecipient to your station.
- To display the Alarm Console, right–click
the ConsoleRecipient and click .
The
Alarm Console opens.

Each record that appears in the alarm console table represents
one alarm source and one or more alarms from that source.
- To silence an alarm, select it and click the Silence button at the bottom of the view.
- To sort the alarms in order of any column, click the column
title (once for ascending, twice for descending).
- To view details about the selected alarm, double-click
the alarm row in the table, select the alarm and click Hyperlink or right-click and select Details from the menu.
- To acknowledge one or more of the alarms, select one or
more and do one of the following:
You may select multiple alarms using the Shift or Ctrl keys.
- To acknowledge the latest (most recent) alarm(s), right-click
the selected alarm(s) and click Alarm Acknowledge Most
Recent or click from the menu.
- To acknowledge all alarms that are reported from a single
source, click or click the Acknowledge All button at the bottom of the console.
The system acknowledges the latest or all alarms from
each selected alarm source.
- To manage the alarm database, double-click the Alarm node under Station in the
Nav tree.
The Database Maintenance view opens.
More information about managing alarms is in the Niagara Alarms Guide