You access this view from the main menu by clicking , followed by double-clicking the NrioNetwork driver, selecting and double-clicking a module, clicking the Point Manager link, clicking the Digital Points tab, followed by clicking the hyperlink on a Digital Input point.
The input facets and proxy extension properties are the same as those documented for other Nrio proxy points.

This window opens when you click the Edit button.
| Property | Value | Description |
|---|---|---|
| True Text | text | Sets up the text to appear when Status for the point is true.
|
| False Text | text | Sets up the text to appear when Status for the point is false.
|

In addition to the standard properties (Status, Fault Cause and Enabled), these properties configure this extension.
| Property | Value | Description |
|---|---|---|
| Conversion | drop-down list | Defines how the system converts proxy extension units to parent point units.
NOTE: In most cases, the standard
Default conversion is best.
|
| Tuning Policy Name | drop-down list (defaults to Default Policy)
|
Selects a network tuning policy by name. This policy defines stale time and minimum and maximum update times. During polling, the system uses the tuning policy to evaluate both write requests and the acceptability (freshness) of read requests. |
| Read Value | read-only true or false |
|
| Write Value | read-only true or false |
|
| Poll Frequency | drop-down list | Configures how frequently the system polls proxy points. |
| Instance | number | Defines the point’s I/O terminal address based on its hardware type.
If duplicated (same instance as same hardware type, same board), the point reports a fault status. If an edit attempt is made to an instance already in use by another proxy point, the system discards the edit, and retains the previous instance value. |
| Ui Type | drop-down list |