To access these properties, expand and double-click ACC.
In addition to the common properties (Status and Fault Cause), this component has these properties.
| Property | Value | Description |
|---|---|---|
| Poll Frequency | drop-down list (defaults to Normal)
|
Selects among three rates (Fast, Normal and Slow) to determine how often to query the component for its value. The network’s
Poll Service or Poll Scheduler defines these rates in hours, minutes and seconds. For example:
This property applies to all proxy points. |
| Object Id | drop-down list and number (from 0 to 4194302) | Identifies each device and component by the type of entity (Object Id) combined with a unique Instance Number.
For devices (controllers, instruments, meters, etc.), |
| Object Name | text in the format name.name.name.name (default includes the entire component path in the station using period (“/) delimiters between parent.child levels) | Identifies a BACnet object. This name should be unique within this specific device.
For components, this name includes the entire component path under the station’s Config using period (.) delimiters between parent.child levels. This enforces (externally) the BACnet requirement for unique names for all objects in a device. For a proxy point, this is the default name in the station. You can shorten or edit |
| Object Type | drop-down list of BACnet objects | Reports the type of object. |
| Facets | Config window or read-only property | Identifies the units used for the current component or point value. These could be parent or child point facets. |
| Enable | true (default) or false |
Activates (true) and deactivates (false) use of the object (network, device, point, component, table, schedule, descriptor, etc.).
|
| Status Flags | read-only indicator and check boxes | Configures four status flags for BACnet. These options are available to enable detection of specific status conditions. |
| Event State | read-only | Reports the status of the event. |
| Out Of Service | true (default) or false |
Affects the BACnet exposure and access of the source component only. In other words, if the source (exported) component is
a proxy point, the equivalent Enabled property in its ProxyExt is not affected.
You can set this property to |
| Scale | drop-down list | |
| Max Pres Value | defaults to +inf | |
| Logging Record | additional properties |