This component is in the bacnet palette, under the folder.
| Property | Value | Description |
|---|---|---|
| Notification Threshold | number (defaults to 10) | Indicates the value that once exceeded by the number of records since the last buffer-ready event was raised, a new buffer-ready event is raised. |
| Records Since Notification | read-only | Reports the number of records generated since notification. |
| Last Notify Record | read-only | Reports the last notification record generated. |
| Alarm Inhibit | check-mark (defaults to the incoming value from the device) | When null is enabled, reports the incoming value from the device. You cannot change this value.
To change this value, click the double-arrow to the right and remove the null check mark. |
| Alarm State | read-only | Displays the current state of the alarm: Normal, Low Limit, High Limit orFault. |
| Alarm Enable | check boxes (defaults to toNormal) | Selects the type of occurrence that generates an alarm.
|
| Acked Transitions | read-only | Reports information about the occurrence. |
| Notify Type | drop-down list (defaults to Alarm)
|
Identifies what happens to trigger a record in the trend log. |
| To Offnormal Times | container | When a point transitions to an offnormal state, reports four pieces of information:
|
| To Fault Times | container for four valuesAlarm Time defaults to null, which means that the event has not occurredAck Time defaults to nullNormal Time defaults to nullCount defaults to zero (0)
|
When a point transitions to a fault state, reports four pieces of information:
|
| To Normal Times | container | Reports four pieces of information related to when a point transitioned to a normal state:
|
| To Normal Text | text | Configures what displays when the component transitions to a normal status. When applicable, text entered for Fault Algorithm, High Limit Text and/or Low Limit Text may override this text.
|
| Hyperlink Ord | chooser | Selects a chooser for locating an alarm source. |
| Alarm Class | drop-down list | Specifies or returns the alarm routing option for the component. |