Alarms (bacnet-BacnetAlarmDeviceExt)

Each BacnetDevice has an Alarms device extension. This extension applies to BACnet event notifications (alarms) sent to the station from a device.
Figure 61.   BacnetAlarmDeviceExt (Alarms) properties
Image

One way to view these properties is to expand BacnetNetwork > BacnetDevice followed by double-clicking the Alarms node in the Nav tree.

Property Value Description
Alarm Class drop-down list Specifies or returns the alarm routing option for the component.
Last Received Time read-only Reports the date-timestamp of the last BACnet event notification received from the device.
Niagara Process Id integer Specifies a process ID, which needs to match the BACnet process identifier used to send notifications to this client station. The default value is 0.