opcUaClient-OpcUaClientAlarmDeviceExt

This component is a child of each OpcUaDevice component.  Each OPC UA device has a frozen slot named AlarmExt that is of type OpcUaClientAlarmDeviceExt.

The default view is the Opc Ua Client Alarm Manager.

This component provides the ability to subscribe to OPC UA alarm events. The view allows you to scan the connected OPC UA server for OPC UA variables that can generate an alarm.

Figure 11.   OpcUaClientAlarmDeviceExt properties
Image

To view these properties, expand Config > Drivers > OpcUaNetwork > OpcUaDevice, right-lick Alarm Ext and click Views > AX Property Sheet.

In addition to the standard properties that configure Alarm Source Info, these properties support the OPC UA client alarm device extension.

Property Value Description
Alarm Class drop-down list (defaults to Medium) Specifies or returns the alarm routing option for the component.
Last Received Time read-only Reports the time the last alarm was received.
Auto Subscribe Enable true (defaul)t or false Turns automatic device subscription on (true) and off (false).
Opc Ua Severity read-only Reports the configuration for the four severity settings. For more information, refer to opcUaServer-OpcUaAlarmRecipient.