Out property. Commands at the emergency and manual levels (1 and 8) are stored persistently.
This point is available in the Points folder of the control palette and usually resides in a device’s Points folder.

You can access these properties by double-clicking the component wherever a Boolean point is used. The point’s characteristic green circle icon with a B in the middle identifies Boolean writable points in the Nav tree and Wire Sheet.
| Property | Value | Description |
|---|---|---|
| Facets | Config Facets window | Define the text to display for the Boolean values:
For example, the facet trueText could display “ON” and the facet falseText “OFF.” You view Facets on the Slot Sheet and edit them from a component Property Sheet by clicking the >> icon to display the Config Facets window. |
| Proxy Ext, Out | message | Provides a current binary value, facets (text descriptors) and data status, such as fault, overridden, alarm, and so on. If no status flag is set, status is considered normal and reports {ok}.The station itself originates the point’s default |
| Proxy Ext, In1–16 | values | Indicate from where the point’s value originates, including details specific to the parentage of the point’s network and communications
(driver).
null indicates that the point is an empty placeholder. |
| Proxy, Fallback | value | Configures a default Out value for a point when a priority scan of inputs In2 – In7 and In9 – In16returns a null or invalid value, and no emergency action (In1) or manual action (In8) has occurred.
|
| Override Expiration | read-only | Reports how long a value that has been set manually (using an action) remains valid. |
| Min Active Time | hours minutes seconds (defaults to 00000h 00m 00s) | Defines a minimum up time.
This property works independently of The default disables the timer. |
| Min Inactive Time | hours minutes seconds (defaults to 00000h 00m 00s) | Defines a minimum down time.
This property works independently of The default disables the timer. |
| Set Min Inactive Time On Start | true or false (default)
|
Determines if the minimum inactive time applies at station start. |
This component supports the following actions:
true and false options, which you can use to manually configure the point’s value.