The OrionAlarmService component is available in the alarmOrion palette.

In addition to the standard properties (Status, Enabled, and Fault Cause), this component provides these properties.
To access, expand and right-click .
| Type | Value | Description |
|---|---|---|
| Alarm Db Config | 1–250,000 records | Defines the number of alarm records to store in the histories database. When the capacity is reached, newer alarm records overwrite the oldest records. |
| Alarm Class | drop-down list (defaults to Medium)
|
Selects an alarm class from the option list. The alarm class specifies the alarm routing options for this component. |
| Master Alarm Instructions | additional properties | Click the Add creates a new instruction. Edit edits a existing instruction. Remove deletes the selected instruction from the list. Move Up/Down changes the order of the instructions in the list. |
| Coalesce Alarms | true or false |
When
NOTE: If sequences or notifications in the Supervisor station are triggered by alarms, you should not coalesce alarms. You do not
coalesce alarms if you may need to document security incidents.
|
| Database | ord | Provides the ord path to the database that is used by the Orion Alarm Service. |
| RdbAlarmDatabaseConversion | additional properties | Configures additional parameters to convert a RDBMS to an Orion database. |