The station recipient component provides a place to specify the location and other details about that remote station. The properties on a station recipient include a field for selecting the remote station, as well as alarm collection options.

| Property | Value | Description |
|---|---|---|
| Time Range, Start Time and End Time | hours:minutes:seconds: | Sets the time of day to begin and stop the function (for example, trigger schedule, alarm event) |
| Days of the Week or Days of Week | check boxes | Specifies the days of the week to include in the function. |
| Transitions | drop-down list | Selects which alarm transitions to display in the console. Only those transitions selected display although the station saves all transitions in alarm history. |
| Status | read-only | Indicates the condition of the network, device or component at the last check.
|
| Last Send Time | time | The date and time the system sent the last alarm to the station. |
| Last Failure Time | time | The date and time of any last failure. |
| Last Failure Cause | text | The reason for the failure. |
| Retry Interval | hours and minutes | In the case of a failed alarm transmission, the amount of time the system waits before attempting to send the alarm to the station again. |
| Queued Alarm Count | number | The number of alarms that are ready to be sent. |
| Remote Station | Displays a list of eligible remote stations. Valid stations have a valid network connection between the
|