Actions on this component include: Route Alarm
| Property | Value | Description |
|---|---|---|
| Time Range | Start Time and End Time | Start Time sets the time of day to begin the function (for example, trigger schedule, alarm event) |
| Days of the Week or Days of Week | check box | Specifies the days of the week for a function to be active. |
| Transitions | Option boxes | Allow selection of specific alarm transitions to display in the console. Only those transitions that are selected will be displayed in the console - even though the alarms are still saved into the alarm history. |
| Route Acks | true or false |
Enables and disables the routing of alarm acknowledgements to the recipient. |
| Enabled | true or false |
Activates and deactivates use of the function. |
| Phone Numbers | phone number international format | Defines the recipient's telephone number. It must be in international format. |
| Body | 140 characters of text | Defines the message itself, which defaults to Source, Text and UUID. You may format the text for the SMS message within the body slot. |