| Information | Value | Description |
|---|---|---|
| Timestamp | hours:minutes:seconds%timestamp% (on a report) | Specifies the date and time the event occurred. |
| Uuid | read-only | Displays the Unique Universal Identifier (UUID) the system uses to uniquely identify the alarm record. |
| Ack State | Acked or Unacked | Indicates if the alarm has been acknowledged. |
| Ack Required | true or false |
Indicates if the alarm must be acknowledged (true) or not (false).
|
| Alarm Class | List, console column, or field or %alarmClass% on a report. | Specifies or returns the alarm routing option for the component. |
| Priority [on-call contact] | 1–255 for each transition, default: 255; %priority% on a report | Specifies the order in which the OnCallService sends alarm notifications to the OnCallContact. Colors graphically identify alarm priority levels. You set up Priority levels using the alarm options window. The contact
with the lowest number (highest priority) receives notification first. An alarm that is not acknowledged within the designated
time is forwarded to the next contact in the list.
NOTE: Contacts may share the same Priority number. The OnCallService sends an identical notification to all contacts that have the same priority number
|
| Normal Time or NormalTime | date and time | Displays the date and time (if applicable) that the alarm state returned to normal. |
| Ack Time | hours:minutes:seconds | Displays the time that the alarm was acknowledged (if applicable). |
| User [provisioning] | text | The station user that requested the job. This column displays unknown if job was triggered by a linked schedule.
|
| Alarm Data | read-only |
Presents a detailed list of alarm data, including this information:
|
| Transitions | toOffnormal, toFault, toNormal, toAlert |
Allows selection of specific alarm transitions to display in the console. Only those transitions that are selected will be displayed in the console - even though the alarms are still saved into the alarm history. |
| Last Update | read-only | Displays the time the system most recently updated the alarm. |